Generator Missing Problem

This topic contains 0 replies, has 1 voice, and was last updated by  Asad Javed 7 years, 11 months ago.

Viewing 1 post (of 1 total)
  • Author
    Posts
  • #1199

    Asad Javed
    Participant

    <p style=”text-align: left;”>Problem Statment: “The Generator Installed at HPT found to show the high variation at Oil Pressure Gauge and missing in operation at machine which was causing abnormal vibration  “</p>
    Root Cause: The root cause found that Diesel Oil intake was not smooth and the Engine oil level was also near below low level.

    Corrective Action:  

    1. The filter at the input line of Diesel oil Replaced to rectify the missing problem at machine which was causing abnormal vibration.
    2. The Engine oil level improved

    Results after Maintenance:  After maintenance activity the Generator being observed regularly during operation and found stability at oil pressure gauge and smooth machine operation without any vibration & missing.